Porcelain

Porcelain Cutout Insulator

porcelain cutout insualtor

Porcelain cutout insulator, as a kind of high voltage insulator, which used on drop out cutout. Cutout, known as fuse, is one kind of connection in the circuit to protect the disposable components of the circuit. When current is excessive ,the metal wire or sheet produce heat and melt, resulting in open and interrupt the current to protect the circuit from harm. It is used in transmission and distribution system and is adapted to serve under the influence of a fault current in order to interrupt the current.

How does the drop out cutout work?

It is melted by its self-generated heat,based on the current exceeds cutout predetermined for a period time,finally the circuit is disconnected. The porcelain cutout insulator won’t damage in this. According this working principle, drop out cutout is widely used on high voltage transmission and distribution system,also protective device. As a short-circuit and over-current protection, it is one of the most common protective devices.

Cutout Insulator Types:

Type No.Rated Voltage
(kV)
Rated Current
(A)
Breaking Current
(A)
BIL
(kV)
Power frequency withstand voltage
(kV)
Leakage Distance
(mm)
Weight
(kg)
OPC12-110-1510010000110402507.3
OPC12-2 10-15 20012000110402507.3
OPC24-12410010000125453508.5
OPC24-22420012000125453508.5
OPC27-12710080001506553012
OPC27-227200100001506553012
OPC33-13310060001807566014
OPC33-23320080001807566014
OPC36-13610010001707080016
OPC36-236200120001707080016


Prev

Next:Porcelain Bushing Insulator

The Latest Article